ProposalWorkspaceFederal OpportunitiesDepartment of Veterans Affairs

J061--Eaton Powerware System Replacement

Active 36C24127Q0030 Combined Synopsis/SolicitationService-Disabled Veteran-Owned Small Business (SDVOSB) Set-Aside (FAR 19.14)Department of Veterans Affairs
The full text, documents and contacts of this bid come with a ProposalWorkspace plan.Get started

At a glance

241-Network Contract Office 01 (36C241) of Department of Veterans Affairs posted this Combined Synopsis/Solicitation on Nov 24, 2026. Responses are due Nov 30, 2026. NAICS 811310 (Commercial and Industrial Machinery and Equipment (except Automotive and Electronic) Repair and Maintenance), product or service code J061 (Maint/Repair/Rebuild of Equipment - Electric Wire, and Power and Distribution Equipment). Set-aside: Service-Disabled Veteran-Owned Small Business (SDVOSB) Set-Aside (FAR 19.14). Place of performance: New Hampshire 03104. Solicitation number 36C24127Q0030.

Solicitation details

General information

Solicitation number
36C24127Q0030
Notice type
Combined Synopsis/Solicitation
Set-aside
Service-Disabled Veteran-Owned Small Business (SDVOSB) Set-Aside (FAR 19.14)
Place of performance
New Hampshire 03104

Classification

NAICS
811310Commercial and Industrial Machinery and Equipment (except Automotive and Electronic) Repair and Maintenance
Product or service
J061Maint/Repair/Rebuild of Equipment - Electric Wire, and Power and Distribution Equipment

Agency

Department
Department of Veterans Affairs
Sub-tier
Department of Veterans Affairs
Office
241-Network Contract Office 01 (36C241)

Description

From SAM.gov
36C24127Q0030 UPS Eaton Powerware System Replacement - RFIs Does the VA require technicians performing quarterly and annual preventive maintenance to be individually factory-certified or authorized by Eaton? Due to the complex nature of the product and criticality - Yes Will documented experience and technical qualifications satisfy the qualification requirement for routine preventive maintenance? See answer to RFI 1 Is direct access to Eaton's proprietary field-service software mandatory for the prime contractor, or may that requirement be fulfilled through an Eaton-authorized service provider supporting specific procedures? Prime Contractor does not require that; That portion can be filled through an Eaton Authorized Technician. Would a contractor be considered technically acceptable if it performs routine maintenance using qualified technicians and subcontracts manufacturer-restricted procedures and startup to Eaton? Yes, minor PM work such as filter changes etc. would be outside the requirement of needing an Eaton Technician. Since Eaton has discontinued the 93E product line, will the VA accept the current Eaton 93PM or another equivalent replacement system meeting the required performance specifications? The VA would accept an Eaton alternative. The goal of the project is to replace existing equipment in-kind with newer model. Does the existing Eaton Powerware 9390 system have an external maintenance bypass (for example, a maintenance bypass panel or a bypass sidecar with maintenance bypass and isolation breakers)? Yes, See photos. Is the replacement expected to include a maintenance bypass sidecar, such as the Eaton 93E 60 kVA bypass sidecar shown in Attachment A, or is it limited to the UPS and Extended Battery Cabinet listed in SOW Section 3.5? The UPS is required to be able to go into maintenance Bypass and maintain power to the computer room during maintenance. What is the kVA rating of the existing unit? The SOW says "Model 80," but the replacement is specified at 60 kVA. Existing UPS is 80KVA. The goal is to replace-in- kind. The 60kVA was utilized as a basis of design. What are the existing input voltage and output voltage? Current system: Eaton Powerware 9390-80 Model 80 AC IN: 208VAC 3W 60Hz 3Phase 240A AC OUT: 208VAC 4W 60Hz 3Phase 222A 78KW 80KVA BYPASS: 208VAC 4W 60Hz 3Phase 222A 80KVA DC: 384-480Vdc 204A Please provide a photo of the existing unit's data plate. See attached photos Please provide photos of the full system (standing back) and of the battery cabinet and batteries. See attached photos Please confirm the battery quantity and model: 40 x Hitachi Chemical Energy Technology 12V 540W, HRC12540WP. Confirmed What is the current battery run time, and what run time is required for the replacement? 60 minutes would it be possible to forward the latest performance specifications/Source Control Drawings for the Powerware System attached Will the VA be paying invoices on a Net-30/45/60 schedule?  The VA approves all invoices within 15 days and funds are transferred within 30 days of receipt.

Documents

12 files

Subscribe to download these 12 files.

  • 36C24127Q0030.docx
    56 KB · Nov 4, 2026
    Download
  • Attachment A - Eaton 93E UPS manufacturer cut sheets and site electrical drawings Start-Up.pdf
    3.6 MB · Nov 4, 2026
    Download
  • Attachment B - Wage Determination No 2015-4019 rev 35.pdf
    4.1 MB · Nov 4, 2026
    Download
  • 36C24127Q0030_1.docx
    17 KB · Nov 10, 2026
    Download
  • 36C24127Q0030_2.docx
    17 KB · Nov 18, 2026
    Download
  • 36C24127Q0030_3.docx
    18 KB · Nov 24, 2026
    Download
  • UPS Drawings and Other Info.pdf
    393 KB · Nov 24, 2026
    Download
  • UPS Eaton PowerWare Replacement Photos.docx
    7.2 MB · Nov 24, 2026
    Download
  • UPS Guide Specification.pdf
    1.0 MB · Nov 24, 2026
    Download
  • UPS Installation Instructions.pdf
    946 KB · Nov 24, 2026
    Download
  • UPS Eaton 9390 product info.pdf
    6.0 MB · Nov 24, 2026
    Download
  • UPS Manual Section II Operation.pdf
    677 KB · Nov 24, 2026
    Download

Similar open bids